Cable Size & Voltage Drop Calculator

Enter your load and run length — get the correct copper conductor size with current rating and voltage drop checked side by side, for single and three phase circuits.

5% is the common limit for final circuits; use 2.5% for motors and sensitive equipment.

Recommended copper conductor
4 mm²

32.0 A load · 10.6 V drop (4.6%) over 30 m

Quote this cable & accessories

Copper conductor comparison — your load on every size

SizeRatingVolt drop%Verdict
1.5 mm²17.5 A27.8 V12.1%Over current
2.5 mm²24 A17.3 V7.5%Over current
4 mm²32 A10.6 V4.6%✓ Recommended
6 mm²41 A7.0 V3.0%OK
10 mm²57 A4.2 V1.8%OK
16 mm²76 A2.7 V1.2%OK
25 mm²101 A1.7 V0.7%OK
35 mm²125 A1.2 V0.5%OK
50 mm²151 A0.9 V0.4%OK
70 mm²192 A0.6 V0.3%OK
95 mm²232 A0.4 V0.2%OK
120 mm²269 A0.3 V0.2%OK
150 mm²309 A0.3 V0.1%OK
185 mm²353 A0.2 V0.1%OK
240 mm²415 A0.2 V0.1%OK
300 mm²477 A0.1 V0.1%OK

Guide values for PVC-insulated copper, clipped direct, 30 °C ambient. Grouping, conduit, high ambient and aluminium conductors change ratings — final selection is confirmed by our engineers to SANS 10142 / your site standard.